Galaxy 2000LD
UPS
        UPS, 2000VA, 240W, 7ahx4, 230/50, With 2 Schuko outlets, RJ45 x2, USB      
      
      
BASIC INFORMATION | 
|
| Type | Online UPS | 
| Part Number (P/N) | POS2178 | 
| EAN | 5600865271734 | 
| Model | Galaxy 2000LD | 
| Color | Black | 
| Outlet type | Shuko | 
| Outlets | 2 outlets with power source | 
| Implementation | Computers, screens and POS | 
| Capacity | 2000VA:1600W | 
TECHNICAL SPECIFICATIONS | 
|
FUNCTIONS | 
|
| Main | Common Neutral design, Double Conversion Topology (O/P Neutral to I/P Neutral is 0 volt normally) Wide Range Input Window and Input Power Factor correction 0.8~0.9 Output Power Factor Low Noise Smart Cooling Fan Design High Efficiency, New Full-bridge Inverter Design Smart backup time estimation (LCD display model) Adjustable floating charging voltage Automatic restart of loads after UPS shutdown Generator compatible Smart battery management  | 
| Outlets | 2 Schuko outlets with power  | 
| Display | YES - Time Remaining, consumption and voltage  | 
INPUT | 
|
| Nominal Voltage | 200V/220V/230V/240V Selectable  | 
| Voltage Range | 100~285V  | 
| Frequency Range | Under Frequency Converter Mode, 40-70Hz  | 
OUTPUT | 
|
| Capacity | 2000VA:1600W  | 
| Output Voltage | 200V/220V/230V/240V Selectable  | 
| Voltage Waveform | Sine Wave  | 
| Crest Factor | 3:1  | 
| Regulation | ±2% of selected output voltage (adjustable by software)  | 
| Transfer Time | AC to DC: Zero Inverter to bypass: 4ms Typical  | 
| Overload Protection | > 100% overload alarm 100%~115% for 60 seconds, then transfer to bypass mode; 115%~135% for 10 seconds, then transfer to by pass mode; >135% for 2 seconds, then transfer to bypass mode; If bypass mode is not available, then UPS will shutdown the O/P power  | 
| AC Mode Efficiency | Up to 92%  | 
BATTERY | 
|
| Type | Maintenance–free sealed, valve-regulated, Lead-Acid 12V, 7Ah or 12V, 9Ah (option)  | 
| Charging Method | CC+CV with trickle charging, voltage 13.2~13.9 adjustable  | 
| Recharge Time | 7 hours to 90%  | 
| Protection | 
 Over current protection.   | 
| 
 Monitoring  | 
 
 Smart monitoring for failed battery or battery open circuit detection and warning   | 
OTHERS | 
|
| Dimensões (WxHxD) | 450x200x180mm  | 
| Peso | 19Kg  | 
| Temperature | Operação: 0ºC~40ºC | Armazenamento: -15ºC~55ºC  | 
| Humidade | 5 - 95% non condensing  | 
| Audible Noise | < 45dB  | 
| Certification | CE  |